DC 2
Data Center
information
Gross size
21,000 m²
Net size
4,800 m²
Power available
2 x 12.6 MVA
IT room height
3.80 m
Raised floor
1.20 m
Floor load
2,000 kg/m²
Equipment elevator
2,500 kg
UPS systems
–
Generator autonomy
48 hours; 24/365 refuel contracts
Power to IT rooms
Average = 1750 W/m²
Power loads
up to 10 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N, N + 1
Cooling specifications
Water input 12° C; output 18° C
PUE
1.25 / 1.35
SLA
99.75% / 99.995%
SECURITY & ACCESS
- Fire and very early smoke detection (VESDA)
- Neutral gas (nitrogen) fire suppression system
- Water leakage detection
- Intrusion detection
- 24/7/365 on-site security guards with controlled access
CONNECTIVITY
- Carrier-neutral
- International & national telecom operators
- Internet exchanges hosted at LuxConnect: NL-ix & LU-CIX